  管道抗震保持体系的布署原则
  Layout Principle of Pipeline Seismic Maintenance System
  (1)管道抗震加固侧向间距要求为:沟槽连接管道、焊接钢管、钎焊铜管等刚性材质的管线,横向吊架间距对照大不得超越12m;HDPE等非刚性材质的管线,横向吊架间距对照大不得超越6m。
  (1) The lateral spacing requirement for seismic reinforcement of pipelines is that the spacing of transverse hangers should not exceed 12 m for pipelines with grooved connection, welded steel pipe and brazed copper pipe, and that of pipelines with non-rigid materials such as HDPE should not exceed 6 m for pipelines with large spacing of transverse hangers.
  (2)管道抗震加固纵向间距要求为:沟槽连接管道、焊接钢管、钎焊铜管等刚性材质的管线,纵向吊架间距对照大不得超24m;HDPE等非刚性材质的管线,横向吊架间距对照大不得超越12m。
  (2) Longitudinal spacing requirements for seismic reinforcement of pipelines are as follows: pipelines with rigid materials such as grooved connection pipelines, welded steel pipes and brazed copper pipes shall not exceed 24m in comparison with longitudinal suspension spacing; pipelines with non-rigid materials such as HDPE shall not exceed 12m in comparison with transverse suspension spacing.
  风管抗震保持体系的布署原则
  Layout Principle of Wind Pipe Seismic Maintenance System
  (1)通常刚性风管侧向抗震吊架的对照大间距为9m,通常刚性风管纵向抗震吊架的对照大间距为18m。
  (1) Generally, the control distance of rigid duct lateral anti-seismic hanger is 9m, and that of rigid duct longitudinal anti-seismic hanger is 18m.
澳门新萄京8522
  (2)玻璃纤维、塑料和其余非刚性材质风管的侧向抗震吊架,对照大间距为4.5m。纵向对照大间距为9m。
  (2) The lateral anti-seismic suspension frame of glass fiber, plastic and other non-rigid air ducts is 4.5m as compared with the large spacing suspension frame. Longitudinal control with large spacing was 9 M.
  电气抗震保持体系的布署原则
  Layout Principles of Electrical Seismic Maintenance System
  (1)刚性电气线管、线槽及桥架侧向抗震对照大间距不得超越12m,纵向抗震对照大间距不得超越24m。
  (1) The large spacing of the lateral seismic control of rigid electrical pipes, grooves and bridges shall not exceed 12m, and that of the longitudinal seismic control shall not exceed 24m.
  (2)非刚性材质电气线管、线槽及桥架横向抗震对照大间距不得超越6m,纵向对照大间距不得超越12m。
  (2) Large spacing of transverse seismic control of non-rigid electrical pipes, grooves and bridges shall not exceed 6m, and large spacing of longitudinal control shall not exceed 12m.
  抗震保持体系计算原则
  Calculation Principles of Seismic Maintenance System
  抗震支吊架的安装模式及布署原则都是依据严格的力学计算后果肯定的,地震力的计算肯定满足规范要求。
  The installation mode and deployment principle of anti-seismic support and hanger are based on strict mechanical calculation, and the calculation of seismic force must meet the requirements of the code.