新萄京8522可在地震中给予机电各体系充分维护,可用于反抗来自水平及垂直方向的地震力的损坏。依据所维护机电体系的不同,抗震支吊架可分为管道新萄京8522体系、风管抗震体系和电气抗震体系。
  Earthquake-resistant brackets can be fully maintained in the earthquake, and can be used to resist damage from horizontal and vertical seismic forces. According to the different mechanical and electrical systems maintained, the anti-seismic brackets can be divided into pipeline anti-seismic bracket system, wind pipe anti-seismic system and electrical anti-seismic system.
  一、新萄京8522分类及布置准则
  Classification and Layout Criteria of Seismic Support
  1.管道抗震加固侧向距离要求为:沟槽衔接管道、焊接钢管、钎焊铜管等刚性原料的管线.横向吊架距离最大不得超越12m;HDPE等非刚性原料的管线,横向吊架距离最大不得超越6m。
  1. The lateral distance requirement of pipeline seismic reinforcement is: pipelines with rigid raw materials such as grooved connection pipeline, welded steel pipe and brazed copper pipe. The maximum distance of transverse hanger should not exceed 12m; pipelines with non-rigid raw materials such as HDPE, the maximum distance of transverse hanger should not exceed 6m.
  2.管道抗震加固纵向距离要求为:沟槽衔接管道、焊接钢管、钎焊铜管等刚性原料的管线,纵向吊架距离最大不得超24m;HDPE等非刚性原料的管线,横向吊架距离最大不得超越12m。
  2. Longitudinal distance of pipeline anti-seismic reinforcement requires: pipelines with rigid raw materials such as grooved connection pipeline, welded steel pipe, brazed copper pipe, etc., the maximum distance of longitudinal hanger shall not exceed 24m; pipelines with non-rigid raw materials such as HDPE, the maximum distance of transverse hanger shall not exceed 12m.
澳门新萄京8522
  二、风管新萄京8522的布置准则
  2. Layout Criteria of Anti-seismic Brackets for Ventilation Pipes
  1.一般刚性风管侧向抗震吊架的最大距离为9m,一般刚性风管纵向抗震吊架的最大距离为18m。
  1. The maximum distance of the general rigid duct lateral anti-seismic hanger is 9m, and the maximum distance of the general rigid duct longitudinal anti-seismic hanger is 18m.
  2.玻璃纤维、塑料和其他非刚性原料风管的侧向抗震吊架,最大距离为4.5m.纵向最大距离为9m。
  2. Lateral anti-seismic suspension of glass fiber, plastic and other non-rigid raw material air ducts, the maximum distance is 4.5 m, and the longitudinal maximum distance is 9 M.
  三、电气新萄京8522的布置准则
  3. Layout Criteria of Electrical Aseismic Support
  1.刚性电气线管、线槽及桥架侧向抗震最大距离不得超越12m,纵向抗震最大距离不得超越24m。
  1. The maximum lateral seismic distance of rigid electrical pipes, grooves and bridge frames shall not exceed 12 m, and the maximum longitudinal seismic distance shall not exceed 24 M.
  2.非刚性原料电气线管、线槽及桥架横向抗震最大距离不得超越6m,纵向最大距离不得超越12m。
  2. The maximum transverse and longitudinal seismic distances of non-rigid electrical pipes, grooves and bridges shall not exceed 6m and 12m.